Balanced three-phase kW, kVA, kVAR and line and phase current from voltage, powe...
https://electrical-calc.x402tookit.com/three-phase-powerOverview
Balanced three-phase kW, kVA, kVAR and line and phase current from voltage, power factor and one of current, kW or kVA.
Protocol
x402
Price
$0.02
Payment Asset
USD Coin
Payment Network
eip155:8453
Category
uncategorized
Provider
Electrical Calculators
Source
bazaar
Indexed
2026-11-01 23:11:57
Health
Status
unknown
Latency (p50)
—
Uptime (30d)
—
Reliability Score
—
Last Checked
Never
Last Healthy
Never
Consecutive Failures
0
x402 Payment Validation
Payment Requirements
—
Asset Verified
—
Facilitator
—
Input Schema
{
"method": "GET",
"queryParams": {
"currentA": 100,
"powerFactor": 0.8,
"voltageV": 400
},
"type": "http"
}
Output Schema
{
"example": {
"asOf": "2026-10-21T06:22:28.988Z",
"degraded": false,
"deltaPhaseCurrentA": 57.73503,
"disclaimer": "Screening signal computed from the named public source. Not financial, legal or investment advice; provided as is. Verify at the source before acting.",
"inputMode": "currentA",
"kva": 69.28203,
"kvar": 41.56922,
"kw": 55.42563,
"kwPerPhase": 18.47521,
"lineCurrentA": 100,
"lineVoltageV": 400,
"notChecked": [
"unbalanced loads, harmonics or distortion power factor",
"leading versus lagging sign (Q is given as a magnitude)",
"…1 more"
],
"phaseAngleDeg": 36.8699,
"powerFactor": 0.8,
"reasons": [
"S = sqrt(3) x V(line-to-line) x I(line) / 1000 in kVA; P = S x PF; Q = S x sin(acos PF).",
"Delta load: phase current = line current / sqrt(3) and phase voltage = line voltage. Wye load: phase current = line current and phase voltage = line voltage / sqrt(3)."
],
"source": "computed locally (S = sqrt(3) V I; P = S cos phi; Q = S sin phi)",
"summary": "400 V three phase: 69.282 kVA = 55.4256 kW + 41.5692 kVAR at power factor 0.8, line current 100 A.",
"verdict": "COMPUTED",
"wyePhaseVoltageV": 230.9401
},
"type": "json"
}