Capacitor kVAR needed to raise power factor from one value to another, with new ...
https://electrical-calc.x402tookit.com/power-factor-correctionOverview
Capacitor kVAR needed to raise power factor from one value to another, with new kVA and current and capacitance per phase.
Protocol
x402
Price
$0.02
Payment Asset
USD Coin
Payment Network
eip155:8453
Category
uncategorized
Provider
Electrical Calculators
Source
bazaar
Indexed
2026-11-01 23:11:57
Health
Status
unknown
Latency (p50)
—
Uptime (30d)
—
Reliability Score
—
Last Checked
Never
Last Healthy
Never
Consecutive Failures
0
x402 Payment Validation
Payment Requirements
—
Asset Verified
—
Facilitator
—
Input Schema
{
"method": "GET",
"queryParams": {
"frequencyHz": 50,
"kw": 100,
"pfFrom": 0.8,
"pfTo": 0.95,
"voltageV": 400
},
"type": "http"
}
Output Schema
{
"example": {
"asOf": "2026-10-21T06:22:28.735Z",
"capacitorKvar": 42.13159,
"currentAfterA": 151.9343,
"currentBeforeA": 180.422,
"degraded": false,
"deltaCapacitancePerPhaseMicroF": 279.3938,
"disclaimer": "Screening signal computed from the named public source. Not financial, legal or investment advice; provided as is. Verify at the source before acting.",
"frequencyHz": 50,
"kvaAfter": 105.2632,
"kvaBefore": 125,
"kvaReduction": 19.73684,
"kvaReductionPct": 15.7895,
"kvarAfter": 32.86841,
"kvarBefore": 75,
"kw": 100,
"notChecked": [
"harmonics and resonance with the supply (detuning reactors may be needed)",
"switching steps and over-correction at light load",
"…1 more"
],
"reasons": [
"Qc = P x (tan(acos PF1) - tan(acos PF2)).",
"Reactive power drops from 75 to 32.868 kVAR.",
"…1 more"
],
"source": "computed locally (Qc = P (tan phi1 - tan phi2); C = Qc / (3 omega V^2) delta)",
"summary": "Raising 100 kW from PF 0.8 to 0.95 needs about 42.132 kVAR of capacitors; apparent power falls from 125 to 105.26 kVA.",
"verdict": "COMPUTED",
"voltageV": 400,
"wyeCapacitancePerPhaseMicroF": 838.1813
},
"type": "json"
}