Overview
Radiator flow rates for hydraulic balancing: from room heat loads and radiator ratings (EN 442 characteristic with exponent) the lowest system flow temperature, required flow per radiator (kg/h, l/h), return temperatures and the critical room. Each radiator output follows Q = Q_N x (dT_ln / dT_ln,N)^n with the logarithmic mean temperature difference dT_ln = (t_v - t_r) / ln((t_v - t_i) / (t_r - t_i)) and the caller’s rating point (default 75/65/20 °C) and exponent.
Protocol
x402 (POST)
Price
$0.0030
Payment Asset
USD Coin
Payment Network
eip155:8453
Category
uncategorized
Provider
rechen
Indexed
2026-11-21 05:10:45
Health
Status
unknown
Latency (p50)
—
Uptime (30d)
—
Reliability Score
—
Last Checked
Never
Last Healthy
Never
Consecutive Failures
0
Input Schema
{
"body": {
"radiators": [
{
"id": "living",
"rated_output_w": 1000,
"room_heat_load_w": 600
},
{
"id": "bedroom",
"rated_output_w": 1500,
"room_heat_load_w": 600
}
]
},
"bodyType": "json",
"method": "POST",
"type": "http"
}
Output Schema
{
"example": {
"limitations": [
"Information computed by formula and statutory rules from the stated parameters; not legal, tax, funding or energy advice and no substitute for planning by a qualified professional.",
"Pipe pressure losses, valve presettings (kv values) and pump selection need manufacturer data and are not computed.",
"The EN 442 characteristic with a constant exponent is an approximation, best near the rating point."
],
"result": {
"assumptions": [],
"constants": {
"cp_kj_kgk": 4.18,
"density": "Kell (1975) at mean water temperature"
},
"critical_radiator": "living",
"legal_basis": {
"checked": "2026-11-01",
"norms": [
"§ 60c GModG (hydraulic balancing duty from six units)",
"BEG EM TMA (hydraulic balancing as funding condition)"
],
"parameters_valid": {
"valid": "physical method, no time-dependent parameters"
},
"sources": [
"https://www.gesetze-im-internet.de/geg/"
],
"version": "GModG as amended by the Act of 23.07.2026; physics per EN 442 characteristic (caller data)"
},
"mixed_return_c": 48.17,
"mode": "lowest_supply",
"radiators": [
{
"covered": true,
"flow_kg_h": 103.35,
"flow_l_h": 104.78,
"id": "living",
"output_at_rating_ratio": 0.6,
"return_c": 51.2,
"room_heat_load_w": 600,
"spread_k": 5
},
{
"covered": true,
"flow_kg_h": 25.36,
"flow_l_h": 25.63,
"id": "bedroom",
"output_at_rating_ratio": 0.4,
"return_c": 35.83,
"room_heat_load_w": 600,
"spread_k": 20.37
}
],
"steps": [
"Lowest flow temperature so that every radiator covers its load with at least 5 K spread: 56.2 °C (critical: living).",
"Each radiator: return temperature from Q_load = Q_N (dT_ln/dT_ln,N)^n; mass flow = Q / (c_p (t_v - t_r))."
],
"supply_temperature_c": 56.2,
"total_flow_kg_h": 128.71,
"undersized": []
},
"service": "hydraulic-balance",
"status": "success"
},
"type": "json"
}